Evaluation of the Aqua-Stream™ Side Stream Filter with Pathex® Antimicrobial Filter Media Part 6: The Economics of Side Stream Filtration

4/24/2018

0 Comments

 
Picture
Picture
Summary of Study:
Beginning in October 2016, AS Filtration, LLC conducted a year-long study to document the effectiveness of a non-oxidizing biocide within a side stream filter on the cooling tower system of a four-story office building in Chattanooga, Tennessee. AS Filtration installed an Aqua-Stream™ side stream filter, utilizing their unique Pathex® antimicrobial filter media, on the 400-ton cooling tower system in operation at the office building. The goal of this study was to analyze the effects of the Aqua-Stream™ and Pathex® on bacteria, energy use, water use, and overall equipment/maintenance costs.

Economics:
Side stream filtration offers savings in energy and water consumption, as well as maintenance and equipment costs. The formula used by the Pacific Northwest National Laboratory in the paper “Side Stream Filtration for Cooling Towers” is applied below to simulate the annual energy cost for a 400-ton cooling tower, similar to the one at the Chattanooga site:

A/C tonnage x kW/ton x load factor x hours of operation/year x cost/kWh = energy costs per year

The cooling tower at the Chattanooga site is a 400-ton tower, this example assigns a 50% operating efficiency, a typical 70% load, 3,500 operating hours per year (roughly 40% of the year), and an energy cost of $0.11 per kWh (the actual cost per kWh at the location during the study, according to supplied records). Using these values, the approximate annual operating cost of $53,900 for this cooling tower is calculated as follows:

400 ton x 0.5 kW/ton x 0.7 load factor x 3,500 hours/year x $0.11/kWh = $53,900/year

The Pacific Northwest National Laboratory anticipated the side stream filter to result in a minimum energy savings of 10%, or $5,390 per year. Also, the frequency of required blowdown was expected to decrease, allowing water to be utilized by the cooling tower roughly 33% longer, saving 228,000 gallons per year. Using a combined water cost of $7 per thousand gallons, the actual average cost at the location, this decrease in water demand would result in water cost savings of $1,596 annually. It was also expected to cut required maintenance in half, leading to a conservative estimate of $2,160 of savings per year. All chemical treatment was removed for the study, relying only on the Aqua-Stream™ and Pathex® for water treatment, saving approximately $1,500 per year in chemicals. In total, the installation of this side stream filtration system on a properly maintained cooling tower would result in an estimated savings of $10,646 annually (PNNL 2012).

Contact AS Filtration to find out more about using the Aqua-Stream™ and Pathex® at your facility!
CONTACT US TODAY!
0 Comments



Leave a Reply.

    Archives

    February 2021
    January 2021
    May 2020
    April 2020
    February 2020
    July 2019
    May 2019
    March 2019
    May 2018
    April 2018
    March 2018
    February 2018
    January 2018
    December 2017
    February 2016
    January 2016
    November 2015
    October 2015
    September 2015
    August 2015
    July 2015
    June 2015
    May 2015
    April 2015
    March 2015
    January 2015

    Categories

    All
    Aqua Stream
    Aqua-Stream
    ASHRAE
    Cooling Tower
    Energy Star
    Filter Media
    Maintenance
    News
    Pathex
    PathShield
    Side Stream Filtration
    Side-stream Filtration
    Water Savings

    RSS Feed